RESIDENTIAL BURNERSPotential for Fire, Smoke and Asphyxiation HazardsTo the Homeowner or Equipment Owner:Please read and carefully follow all instruct
10Note: to determine the proper fuel line size, refer to the fuel pump manufacturer’s instructions provided with the burner. Refer to Figure 6 or Figu
11SF/SM Burner ManualFuel supply below the level of the burner –When the fuel supply is more than eight feet below the level of the burner, a two-pipe
12Burner ControlsGeniSys Model 7505 ControlWiringFigure 8 - 7505 Control FeaturesThermostat / Operating and Limit Control CompatibleWelded Relay Prote
13SF/SM Burner Manualthe igniter remains on for 10 additional seconds to ensure fl ame stability. Run: The fl ame is sustained until the call for heat
14Figure 9a. – Interrupted ignition, valve-on delay only (no motor-off delay)Figure 9b. – Interrupted ignition, valve-on delay and motor-off delaySAFE
15SF/SM Burner ManualRECYCLE. If the fl ame is lost while the burner is fi ring, the control shuts down the burner, enters a 60 second recycle delay, an
16Start Up Burner/Set CombustionExplosion and Fire Hazard Failure to follow these instructions could lead to equipment malfunction and result in heavy
17SF/SM Burner ManualOIL-BURNING EQUIPMENT SHALL BE CONNECTED TO FLUES HAVING SUITABLE PRESSURE (DRAFT) AT ALL TIMES TO ASSURE SAFE AND PROPER OPERATI
18CENTER WHEEL FOR EQUAL DISTANCE FROM HOUSING SIDESSection: Perform Regular MaintenanceALWAYS KEEP THE FUEL OIL SUPPLY VALVE SHUT OFF IF THE BURNER(S
19SF/SM Burner Manual# Part No. Description1 Burner Housing Assembly with Inlet Bell2 3215 Air shutter, 10 Slot3 3819 Bulk Air Band, 10 Slot 4 3493 No
2To the Owner:Thank you for purchasing a Beckett burner for use with your heating appliance. Please pay attention to the Safety Warnings contained wi
USA: P.O. Box 1289 ● Elyria, Ohio 44036Canada: R.W. Beckett Canada, Ltd. ● Unit #3, 430 Laird Road ● Guelph, Ontario N1G 3X7www.beckettcorp.comPart Nu
3SF/SM Burner ManualSection: General InformationGeneral InformationHazard Defi nitions Within the boundaries of the hazard warning, there will be infor
4Section: General InformationTable 1 – Burner Specifi cationsModel SM Capacity (Note1)Firing rate range: 01.25 – 3.00 GPH Input: 175,000 – 420,000 Btu/
5SF/SM Burner ManualInspect/Prepare Installation SiteSection: Inspect/Prepare Installation SiteSpecial RequirementsTHE INSTALLATION OF A BURNER SHALL
6Inspect chimney or direct vent systemStarting with minimum gph fi ring rate, the minimum size recommended is 6” fl ue pipe with 8” X 8” inside chimney,
7SF/SM Burner ManualInstall burner nozzle (if not already installed) Exhaust fans and other air-using devicesSize air openings large enough to allow f
8Mount Burner on ApplianceMounting optionsTable 4. Nozzle Flow Rate by SizeNozzle fl ow rate U. S. gallons per hour of No. 2 fuel oil when pump pressur
9SF/SM Burner Manual1-1/8” PLUS SHROUD LENGTHZDIM.1-1/8” Dimension (inches)F HeadA = Usable air length (inches) (Measure accurately)L (Total tube leng