RESIDENTIAL BURNERS
Potential for Fire, Smoke and Asphyxiation Hazards
To the Homeowner or Equipment Owner:
Please read and carefully follow all instructions
provided in this manual regarding your
responsibilities in caring for your heating
equipment.
Contact a professional, quali ed service agency for
installation, start-up or service work.
Save this manual for future reference.
y
y
y
Incorrect installation, adjustment, or misuse of this burner could result in death, severe
personal injury, or substantial property damage.
To the Professional, Quali ed Installer or Service Agency:
Please read and carefully follow all instructions provided
in this manual before installing, starting, or servicing this
burner or heating system.
The Installation must be made in accordance with all state
and local codes having jurisdiction.
y
y
Przeglądanie stron 0
1 2 3 4 5 6 ... 19 20

Podsumowanie treści

Strona 1 - RESIDENTIAL BURNERS

RESIDENTIAL BURNERSPotential for Fire, Smoke and Asphyxiation HazardsTo the Homeowner or Equipment Owner:Please read and carefully follow all instruct

Strona 2 - Contents

10Note: to determine the proper fuel line size, refer to the fuel pump manufacturer’s instructions provided with the burner. Refer to Figure 6 or Figu

Strona 3 - General Information

11SF/SM Burner ManualFuel supply below the level of the burner –When the fuel supply is more than eight feet below the level of the burner, a two-pipe

Strona 4 - Water Damage Hazard

12Burner ControlsGeniSys Model 7505 ControlWiringFigure 8 - 7505 Control FeaturesThermostat / Operating and Limit Control CompatibleWelded Relay Prote

Strona 5 - Installation Site

13SF/SM Burner Manualthe igniter remains on for 10 additional seconds to ensure fl ame stability. Run: The fl ame is sustained until the call for heat

Strona 6 - Minimum Clearence: 2 FT

14Figure 9a. – Interrupted ignition, valve-on delay only (no motor-off delay)Figure 9b. – Interrupted ignition, valve-on delay and motor-off delaySAFE

Strona 7 - Prepare the Burner

15SF/SM Burner ManualRECYCLE. If the fl ame is lost while the burner is fi ring, the control shuts down the burner, enters a 60 second recycle delay, an

Strona 8 - Mount Burner on Appliance

16Start Up Burner/Set CombustionExplosion and Fire Hazard Failure to follow these instructions could lead to equipment malfunction and result in heavy

Strona 9 - Adjust the ‘Z’ dimension to

17SF/SM Burner ManualOIL-BURNING EQUIPMENT SHALL BE CONNECTED TO FLUES HAVING SUITABLE PRESSURE (DRAFT) AT ALL TIMES TO ASSURE SAFE AND PROPER OPERATI

Strona 10 - Tilt down 2

18CENTER WHEEL FOR EQUAL DISTANCE FROM HOUSING SIDESSection: Perform Regular MaintenanceALWAYS KEEP THE FUEL OIL SUPPLY VALVE SHUT OFF IF THE BURNER(S

Strona 11 - Wire Burner

19SF/SM Burner Manual# Part No. Description1 Burner Housing Assembly with Inlet Bell2 3215 Air shutter, 10 Slot3 3819 Bulk Air Band, 10 Slot 4 3493 No

Strona 12 - Burner Controls

2To the Owner:Thank you for purchasing a Beckett burner for use with your heating appliance. Please pay attention to the Safety Warnings contained wi

Strona 13 - SF/SM Burner Manual

USA: P.O. Box 1289 ● Elyria, Ohio 44036Canada: R.W. Beckett Canada, Ltd. ● Unit #3, 430 Laird Road ● Guelph, Ontario N1G 3X7www.beckettcorp.comPart Nu

Strona 14 - Reset Button Operation

3SF/SM Burner ManualSection: General InformationGeneral InformationHazard Defi nitions Within the boundaries of the hazard warning, there will be infor

Strona 15

4Section: General InformationTable 1 – Burner Specifi cationsModel SM Capacity (Note1)Firing rate range: 01.25 – 3.00 GPH Input: 175,000 – 420,000 Btu/

Strona 16 - Combustion

5SF/SM Burner ManualInspect/Prepare Installation SiteSection: Inspect/Prepare Installation SiteSpecial RequirementsTHE INSTALLATION OF A BURNER SHALL

Strona 17 - (2.6% O

6Inspect chimney or direct vent systemStarting with minimum gph fi ring rate, the minimum size recommended is 6” fl ue pipe with 8” X 8” inside chimney,

Strona 18 - Perform Regular Maintenance

7SF/SM Burner ManualInstall burner nozzle (if not already installed) Exhaust fans and other air-using devicesSize air openings large enough to allow f

Strona 19 - Beckett replacement parts

8Mount Burner on ApplianceMounting optionsTable 4. Nozzle Flow Rate by SizeNozzle fl ow rate U. S. gallons per hour of No. 2 fuel oil when pump pressur

Strona 20 - Limited Warranty Information

9SF/SM Burner Manual1-1/8” PLUS SHROUD LENGTHZDIM.1-1/8” Dimension (inches)F HeadA = Usable air length (inches) (Measure accurately)L (Total tube leng